SRI NEEVI POWER CONTROLS

Loading

STATIC VAR GENERATOR

The principle of the SVG is very similar to that of the Active Power Filter, as demonstrated in the picture below. When the load is generating inductive or capacitive current, it makes the load current lag behind or lead the voltage. SVG detects the phase angle difference and generates leading or lagging current into the grid, making the phase angle of current almost the same as that of voltage on the transformer side, which means the fundamental power factor is unit.

Sri Neevi PQC Series SVG is also modular in design, and the Sri Neevi SVG system consists of one or several SVG modules and an optional Liquid Crystal Monitor & Control Panel (LCM). Each SVG module is an independent reactive power compensation system, and users can change the SVG rating by adding or removing SVG modules.

SVG modules and LCM panel can be embedded in the Sri Neevi standard SVG cabinet or in a customised cabinet. There are usually breakers, cable terminals and a Surge Protection Device (SPD) in the SVG cabinet.

Features & Electrical Specification

Features & Benefits

  • Multifunctional: Reactive power and imbalance compensation
  • High-speed, precise (-0.99 ≤ Cosφ ≤ 0.99), step-less, bi-directional compensation
  • Negative & zero sequence imbalance correction, reduces neutral current
  • Wide input voltage & frequency range for tough environments
  • Low thermal loss (≤3%), efficiency ≥ 97%
  • Modular design for standard or customized cabinets
  • High stability with infinite grid impedance, avoids harmonic resonance
  • Easy installation & maintenance; simple module replacement
  • Wide capacity range: 50–350kvar per cabinet, up to 10 cabinets in parallel
  • Works in 10–50°C environment, diesel generator compatible
  • Full protection: over/under voltage, over current, over temperature
  • Event log for easy troubleshooting
APF Image

Electrical Specification

ParameterDetails
Rated VoltageAC 400V
Input Voltage RangeAC 308V ~ 480V
Electric Connection3P3W / 3P4W
Rated Frequency50(60)Hz ±10%
Rated Capacity per Module50kvar
Rated Capacity per Cabinet50–350kvar (module combination)
RedundancyIndependent reactive compensation module system
Reactive Power CompensationInductive & capacitive, Cosφ ≥ 0.99
Response Time Full: <20ms
Instant: <100µs
Thermal Loss≤ 3% of SVG rated capacity
Output Current LimitationAutomatic (100% rated capacity)
Parallel ExpansionUp to 10 racks (7 modules per cabinet)
MTBF> 100,000 hours
Control Technology – Card Grid

Control Technology & Specifications

Control Technology

  • Switching Frequency: 30kHz
  • Controller: DSP control
  • Communication: Modbus Protocol, RS232/485
  • Monitoring: PQC Monitor Software (Optional)

Physical Specification

  • IP Grade of Cabinet: IP20, IP30 or customization
  • Cooling Method: Intelligent forced air cooling
  • Noise Level: < 60dB(A) @1m (Module)
  • Dust Filter: Optional
  • Dimension: Refer to SVG Model table
  • Weight: Refer to SVG Model table

Environmental Requirement

  • Ambient Temperature: -10 ~ 50°C
  • Relative Humidity: 0 ~ 95%
  • Altitude: ≤ 1000m rated capacity
    1000–2000m (derating 1% per 100m)